Construction and Measurements of an Improved Vacuum-Swing-Adsorption Radon-Mitigation System
arXiv:1506.00929 · doi:10.1063/1.4928027
Abstract
In order to reduce backgrounds from radon-daughter plate-out onto detector surfaces, an ultra-low-radon cleanroom is being commissioned at the South Dakota School of Mines and Technology. An improved vacuum-swing-adsorption radon mitigation system and cleanroom build upon a previous design implemented at Syracuse University that achieved radon levels of 0.2Bqm. This improved system will employ a better pump and larger carbon beds feeding a redesigned cleanroom with an internal HVAC unit and aged water for humidification. With the rebuilt (original) radon mitigation system, the new low-radon cleanroom has already achieved a 300 reduction from an input activity of Bqm to a cleanroom activity of Bqm.
5 pages, 4 figures, Proceedings of Low Radioactivity Techniques (LRT) 2015, Seattle, WA, March 18-20, 2015
References in corpus (5)
- Search for Low-Mass WIMPs with SuperCDMS
- Radiogenic and Muon-Induced Backgrounds in the LUX Dark Matter Detector
- Removal of long-lived Rn daughters by electropolishing thin layers of stainless steel
- The BetaCage, an ultra-sensitive screener for surface contamination
- Construction and measurements of a vacuum-swing-adsorption radon-mitigation system