Revisiting Voltage and Synchronization Stability Analysis in Grid-Following Converter-Integrated Weak Grids: Insights from Non-Minimum-Phase Zeros
arXiv:2605.13061
Abstract
The increasing penetration of grid-following (GFL) converter-interfaced generators (CIGs) intensifies concerns over small-signal voltage and synchronization stability. While existing theories treat these two stability issues distinctly, practical wisdom in contrast employs a unified and static metric, short-circuit ratio (SCR), to assess both in weak grids. This paper aims to bridge this theory-practice gap by introducing the insight of non-minimum-phase (NMP) zeros. First, we demonstrate that the two stability issues in weak grids can be characterized within a common NMP-zero-based assessment framework: a zero at the origin corresponds to voltage instability, while low-frequency zeros impose fundamental constraints on synchronization dynamics. The traditional SCR is proven to be a special case of our proposed novel stability metric, NMP-zero (NMP-Z) factor, evaluated at the rated operating point. This establishes the theoretical foundation for the empirical success of SCR. Building on this insight, we then develop a unified stability assessment method for multi-converter systems. The method retains the simplicity of SCR, requiring only the NMP-Z factor together with individual CIG dynamic models and enabling stability margin assessment under various operating points. Our work provides a simple yet theoretically rigorous framework for stability analysis in CIG-integrated weak grids, with all theoretical findings and the proposed method validated through detailed time-domain simulations.
This manuscript has been submitted to the IEEE Transactions on Power Systems