paper

Pitfalls of Zero Voltage Values in Optimal Power Flow Problems

arXiv:2211.03969

Abstract

The existence of strictly positive lower bounds on voltage magnitude is taken for granted in optimal power flow problems. Nevertheless, it is not possible to rely on such bounds for a variety of real-world network optimization problems. This paper discusses a few issues related to 0 V assumptions made during the process of deriving optimization formulations in the current-voltage, power-voltage and power-lifted-voltage variable spaces. The differences between the assumptions are illustrated for a 2-bus 2-wire test case, where the feasible sets are visualized. A nonzero relaxation gap is observed for the canonical multiconductor nonlinear power-voltage formulation. A zero gap can be obtained for the branch flow model semi-definite relaxation, using newly proposed valid equalities.

arXiv comment5 pages. Submitted to 2023 IEEE PES General Meeting