Abstract
A major risk of geomagnetic disturbances (GMDs) is cascading failure of electrical grids. The modeling of GMD events and cascading outages in power systems is difficult, both independently and jointly, because of the many different mechanisms and physics involved. This paper introduces a relaxation based modeling of GMD-induced cascading failures:~the dc approximation-based DCSIMSEP solver was adapted to simulate cascading as a result of GMDs, the full set of ac power flow equations were relaxed to guarantee optimality, and the reactive power losses were modeled while keeping the problem convex. The developed algorithm was implemented in PowerModelsGMD.jl - an open-source software specifically designed to model and analyze geomagnetic hazards - and demonstrated to work on the RTS-GMLC-GIC-EAST synthetic test network.
arXiv comment7 pages. 5 figures. 3 tables
References in corpus (6)
- Dynamic Modeling of Cascading Failure in Power Systems
- A Markovian influence graph formed from utility line outage data to mitigate large cascades
- A Policy Switching Approach to Consolidating Load Shedding and Islanding Protection Schemes
- The Risk of Hidden Failures to the United States Electrical Grid and Potential for Mitigation
- Analyzing and Mitigating the Impacts of GMD and EMP Events on the Electrical Grid with PowerModelsGMD.jl
- Optimal Transmission Line Switching under Geomagnetic Disturbances