Optimal placement of inertia and primary control : a matrix perturbation theory approach
arXiv:1906.06922 · doi:10.1109/ACCESS.2019.2945475
Abstract
The increasing penetration of inertialess new renewable energy sources reduces the overall mechanical inertia available in power grids and accordingly raises a number of issues of grid stability over short to medium time scales. It has been suggested that this reduction of overall inertia can be compensated to some extent by the deployment of substitution inertia - synthetic inertia, flywheels or synchronous condensers. Of particular importance is to optimize the placement of the limited available substitution inertia, to mitigate voltage angle and frequency disturbances following a fault such as an abrupt power loss. Performance measures in the form of H2-norms have been recently introduced to evaluate the overall magnitude of such disturbances on an electric power grid. However, despite the mathematical conveniance of these measures, analytical results can be obtained only under rather restrictive assumptions of uniform damping ratio, or homogeneous distribution of inertia and/or primary control in the system. Here, we introduce matrix perturbation theory to obtain analytical results for optimal inertia and primary control placement where both are heterogeneous. Armed with that efficient tool, we construct two simple algorithms that independently determine the optimal geographical distribution of inertia and primary control. These algorithms are then implemented on a model of the synchronous transmission grid of continental Europe. We find that the optimal distribution of inertia is geographically homogeneous but that primary control should be mainly located on the slow modes of the network, where the intrinsic grid dynamics takes more time to damp frequency disturbances.
arXiv comment9 pages, 2 figures
References in corpus (8)
- Optimal Placement of Virtual Inertia in Power Grids
- The Key Player Problem in Complex Oscillator Networks and Electric Power Grids: Resistance Centralities Identify Local Vulnerabilities
- Robustness of Synchrony in Complex Networks and Generalized Kirchhoff Indices
- Design of optimal sparse interconnection graphs for synchronization of oscillator networks
- On Placement of Synthetic Inertia with Explicit Time-Domain Constraints
- Transient Performance of Electric Power Networks under Colored Noise
- Graph Laplacian Spectrum and Primary Frequency Regulation
- A Performance and Stability Analysis of Low-inertia Power Grids with Stochastic System Inertia
Cited by in corpus (10)
- Primary Control Effort under Fluctuating Power Generation in Realistic High-Voltage Power Networks
- A large synthetic dataset for machine learning applications in power transmission grids
- Stabilizing Large-Scale Electric Power Grids with Adaptive Inertia
- Finite-time Correlations Boost Large Voltage-Angle Fluctuations in Electric Power Grids
- Long Wavelength Coherency in Well Connected Electric Power Networks
- Dynamic stability of electric power grids: Tracking the interplay of the network structure, transmission losses and voltage dynamics
- Reinforcement Learning Optimizes Power Dispatch in Decentralized Power Grid
- Dispatch of Virtual Inertia and Damping: Numerical Method with SDP and ADMM
- Matrix Perturbation Theory of Inter-Area Oscillations
- Dynamic Droop Control in Low-inertia Power Systems