Stability Region Estimation Under Low Voltage Ride Through Constraints using Sum of Squares
arXiv:1706.09703 · doi:10.1109/NAPS.2017.8107353
Abstract
The increasing penetration of inverter based renewable generation (RG) in the form of solar photo-voltaic (PV) or wind has introduced numerous operational challenges and uncertainties. According to the standards, these generators are made to trip offline if their operating requirements are not met. In an RG-rich system, this might alter the system dynamics and/or cause shifting of the equilibrium points to the extent that a cascaded tripping scenario is manifested. The present work attempts at avoiding such scenarios by estimating the constrained stability region (CSR) inside which the system must operate using maximal level set of a Lyapunov function estimated through sum of squares (SOS) technique. A time-independent conservative approximation of the LVRT constraint is initially derived for a classical model of the power system. The proposed approach is eventually validated by evaluating the stability of a 3 machine test system with trip-able RG.
To appear in "North American Power Symposium, Morgantown, WV, 2017."
Cited by in corpus (4)
- Critical Clearing Time Sensitivity for Inequality Constrained Systems
- Estimating Relevant Portion of Stability Region using Lyapunov Approach and Sum of Squares
- Critical Clearing Time Sensitivity for Inequality Constrained Systems
- Transient Stability Assessment of Cascade Tripping of Renewable Sources Using SOS