Optimal Sizing and Placement of Distributed Storage in Low Voltage Networks
arXiv:1512.01218 · doi:10.1109/PSCC.2016.7540850
Abstract
This paper proposes a novel algorithm to optimally size and place storage in low voltage (LV) networks based on a linearized multiperiod optimal power flow method which we call forward backward sweep optimal power flow (FBS-OPF). We show that this method has good convergence properties, its solution deviates slightly from the optimum and makes the storage sizing and placement problem tractable for longer investment horizons. We demonstrate the usefulness of our method by assessing the economic viability of distributed and centralized storage in LV grids with a high photovoltaic penetration (PV). As a main result, we quantify that for the CIGRE LV test grid distributed storage configurations are preferable, since they allow for less PV curtailment due to grid constraints.
accepted for 19th Power Systems Computation Conference 2016, Genoa, Italy
Cited by in corpus (7)
- Data-driven Local Control Design using Optimization and Machine Learning Techniques
- Optimal Placement and Sizing of Distributed Battery Storage in Low Voltage Grids using Receding Horizon Control Strategies
- Modeling and Optimal Operation of Distributed Battery Storage in Low Voltage Grids
- Linear/Quadratic Programming-Based Optimal Power Flow using Linear Power Flow and Absolute Loss Approximations
- A hybrid approach for planning and operating active distribution grids
- Sizing and Placement of Battery Energy Storage Systems and Wind Turbines by Minimizing Costs and System Losses
- Impacts of Community and Distributed Energy Storage Systems on Unbalanced Low Voltage Networks